HuaRuiDi Science & Technology Co., Ltd.
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
POWER Castle Series Online UPS 5-6 Kva-120Vdc
1.DSP control ,with excellent performance and comprehensive protections for load and UPS ; 2. Output power factor 0.8,offering more stronger load capability;
3.Intelligent fan speed control ,with 4 levels varying according to load and temperature;
4.Wide input range ,support kinds of generator;
5.Compact size and 120Vdc. Less batteries quantity, more economy, safety and easy use;
6. EPO(emergency power off);
7.Event log up to 100 events, recording UPS running time and critical memories ;
8.Intelligent N+X parallel redundancy, up to 6units
9.AC and cold start function;
10. Human friendly large LCD, with plenty operation information
11. Multiple communication ports (optional)
12. Maintenance bypass (option)
Technical Specification
Model |
PCN05S |
PCN05L |
PCN06S |
PCN06L |
|||||
Capacity(Kva/kW) |
5KVA/4.0kW |
5KVA/4.0kW |
6KVA/4.8kW |
6KVA/4.8kW |
|||||
Phase |
1/1PHASE, 1wire+N+G |
||||||||
Input PF |
≥0.99 |
||||||||
Input voltage |
Low transfer |
L-N:176 VAC ± 3% @ 100% load;130 VAC ± 3% @ 50% load |
|||||||
Low back |
L-N:188 VAC ± 3% @ 100% load,142 VAC ± 3% @ 50% load |
||||||||
High transfer |
L-N:286 VAC ± 3% |
||||||||
High back |
L-N:270 VAC ± 3% |
||||||||
Input frequency range |
40-70hz |
||||||||
Battery |
|||||||||
Rating/type |
12V/9Ah |
depend on external battery |
12V/9Ah |
depend on external Battery |
|||||
quantity |
10 |
depend on external battery |
10 |
depend on external Battery |
|||||
Back up time |
4-10mins (depends on load) |
3-8mins (depends on load) |
|||||||
DC voltage |
120Vdc |
||||||||
Charge voltage |
137Vdc |
||||||||
Recharging current |
1A |
5/10A |
1A |
5/10A |
|||||
Output |
|||||||||
Output P.F |
0.8 |
||||||||
Output voltage |
220/230/240Vac +/-1%(static) |
||||||||
Frequency |
46~54Hz or 56~64Hz (Line mode) |
||||||||
Crest factor |
3:1(max) |
||||||||
Wave distortion |
Less than 2%(linear load), Less than 4% Non-linear load |
||||||||
Over load |
105%<load<125% for 1 mins ,125%<load<150% for30sec |
||||||||
Efficiency |
90%(full load) |
||||||||
Transfer time |
0ms (AC-Battery); |
||||||||
0 ms(bypass-inverter) |
|||||||||
Indicator |
|||||||||
LCD Panel |
UPS status, Load l Related Search
Online UPS
Online Interactive Ups
Online Power Supply
Ups Power
Ups Power Transformer
Ups Power Backup
More>>
Find more related products in following catalogs on Hisupplier.comRelated Products
|